What Size Steel Tube for Patio Cover Beams and Posts?

Attached steel patio cover with square tube posts and a rectangular tube beam set on edge behind a desert ranch house.

Most steel patio covers use square tube for the posts and a deeper rectangular tube, set on edge, for the beam. The exact size depends on your span, the loads your building department sets, and how the cover ties into the house and the ground. An engineer or an approved plan decides what size steel tube for patio cover framing goes on your permit.

What you can do is walk in knowing the inputs: the loads, the stiffness of common tube, and what a longer span does.

Why there is no steel tube span table for patio covers

There is no published span table for steel tube patio covers because a custom steel cover is designed for its own site. The span tables you will find are for wood framing and for pre-engineered aluminum kits. Riverside County’s over-the-counter permit for Alumawood covers, for example, asks for drawings stamped and signed by the engineer, a site plan with post spacing and overhang, and the post spacing table from those drawings. If a design goes past the limits in the kit drawings, formal plan review may be required.

Mohave County requires two sets of stamped engineered plans for steel buildings and steel carports, and wants steel buildings designed and inspected to AISC 360, the American Institute of Steel Construction (AISC) steel design standard. Ask the county whether your steel patio cover falls under that rule. Nobody can honestly tell you a 4×4 spans so many feet without knowing your site.

The three numbers your building department sets

In California, patio covers have their own appendix in the Residential Code (Appendix BF in the 2025 edition, Appendix AH in earlier ones). BF105.1 says a cover must carry all dead loads plus a vertical live load of at least 10 psf (pounds per square foot), with snow load used where it is higher, and the wind loads of Section R301.2.1. The same appendix caps a patio cover at one story and 12 feet in height. It also says a cover is for outdoor living, not a carport, garage, storage room or living space.

That gives you three inputs:

  1. Vertical load. 10 psf live load at minimum, or the snow load if it is higher.
  2. Wind. A basic wind speed and an exposure category, set by your jurisdiction and your site. Exposure C, the category you will see below, means open terrain with few obstructions, which takes more wind.
  3. What carries the posts. In areas with no frost depth, BF105.2 lets a cover sit on a slab without footings only if the slab is at least 3.5 inches thick and each column carries no more than 750 lb of live plus dead load. Above that, you need footings.

Arizona works differently. Mohave County’s residential page gives its steel building criteria under the 2018 International Building Code and posts its own handouts for open patio covers. If you are building around Ft. Mohave, ask the county which patio cover rules apply to a steel cover before you borrow the California numbers above.

These are the values published around our three branches. Your address can differ.

AreaGround snowWindSource
High Desert (Victorville, next to Hesperia)5 psf100 to 115 mph by occupancy, most at 110 mph, Exposure CCity of Victorville Building Division
San Bernardino County (unincorporated)From the ASCE 7 Hazard Tool for your siteExposure C minimum countywide; site speed from the Hazard ToolSB County bulletin IB-0003
Thousand Palms and other Coachella Valley townsAsk the countyMay fall in a special wind region: 130 mph for Risk Category I and II (ordinary homes and accessory structures), Exposure CRiverside County handout 284-203 (2021)
Mohave County, AZ0 psf up to 3,000 ft, 5 psf from 3,000 to 4,500 ft, 10 psf from 4,500 to 5,400 ft95 mph, Exposure CMohave County Building Division (steel building criteria)

Two cautions. First, the 130 mph Coachella Valley figure comes from Riverside County’s 2021 handout, written under the 2019 code. Newer codes have been adopted since, so confirm the current number before anyone runs calcs. Second, Hesperia is its own city with its own Building & Safety Division, and patio covers are on its list of work that needs a permit. Ask the city for its criteria.

Common square and rectangular tube, by the numbers

HSS (hollow structural section) is the standard name for structural square and rectangular tube. The moment of inertia (I) measures stiffness, which controls sag. The section modulus (S) relates to bending strength. These figures come from Atlas Tube’s published tables for ASTM A500 tube (squares and rectangles). For rectangular tube, the values are about the strong axis, with the tall side vertical.

Tube (HSS)Weight (lb/ft)I (in4)S (in3)
3x3x1/84.751.781.19
3x3x3/166.872.461.64
3x3x1/48.813.022.01
4x4x.1206.214.272.14
4x4x1/86.464.402.20
4x4x3/169.426.213.11
4x4x1/412.217.803.90
6x2x3/16 (on edge)9.4210.53.50
6x3x3/16 (on edge)10.7013.44.47
6x4x3/16 (on edge)11.9716.45.47
8x4x3/16 (on edge)14.5333.18.28

For the material, the Steel Tube Institute recommends ASTM A500 Grade C, with a 50 ksi (50,000 pounds per square inch) minimum yield, as the default for structural tube. A500 allows a 10 percent wall tolerance, so AISC has designers use 0.93 times the nominal wall for welded A500 tube. The Atlas numbers already account for that. ASTM A513 is mechanical tubing with no minimum yield in its main body. STI recommends keeping it for nonstructural uses, which makes it the wrong pick for a beam or post.

A worked example: 12 ft vs 16 ft span

This is an illustrative example, not a design. It checks how much a beam sags under the 10 psf live load, plus one rough look at bending stress. It does not check buckling, wind uplift, seismic, welds, base plates, anchors or footings.

The setup: an attached cover where one beam sits on two posts and carries 6 feet of roof width (half of a 12 ft rafter run). At 10 psf that is 60 lb per foot of beam. Steel’s modulus of elasticity is 29,000 ksi per the AISC 360-16 Specification. For a simple beam with an even load, the standard formula for the most sag at midspan is 5wL4 / 384EI.

For the yardstick, the residential code’s deflection table, CRC Table R301.7, limits all other structural members to L/240. It allows L/180 only for rafters steeper than 3:12 with no finished ceiling attached, which doesn’t describe a typical low-slope cover beam. L/240 works out to 0.60 inch at 12 feet and 0.80 inch at 16 feet.

Beam tube (HSS)Sag at 12 ft spanSag at 16 ft span
3x3x3/160.39 in (L/367)1.24 in (L/155), over L/240
4x4x1/80.22 in (L/656)0.69 in (L/277)
4x4x3/160.16 in (L/926)0.49 in (L/391)
6x2x3/16 on edge0.09 in (L/1566)0.29 in (L/661)
6x3x3/16 on edge0.07 in (L/1999)0.23 in (L/843)

Look at any row. Going from 12 feet to 16 feet adds a third to the span, yet the sag more than triples. Span sits in the formula to the fourth power, and (16/12)4 is about 3.2. That is why adding a post in the middle of a long beam often does more than buying heavier tube.

Bending strength is not the problem here. Using the AWC formula for the largest bending moment, wL2/8, the 16 ft beam sees 60 x 16 x 16 / 8 = 1,920 lb-ft, or 23,040 lb-in. Divide by the S of 3.11 for a 4x4x3/16 and you get about 7,400 psi, or 7.4 ksi, against a 50 ksi yield. This is not a design check: it has no safety factors, no buckling, no wind and no connections. It shows that here, stiffness runs out long before strength.

Sag limits also don’t cover drainage: the commercial code’s deflection table, IBC Table 1604.3, has a footnote that its limits do not protect against ponding on low-slope roofs.

Sizing the beam: go deeper, not thicker

For the same steel, a deeper tube set on edge beats a thicker square tube. An HSS 6x2x3/16 and an HSS 4x4x3/16 weigh the same, 9.42 lb per foot. Turn the 6×2 on edge and its I is 10.5, against 6.21 for the 4×4. That is about 1.7 times the stiffness, or 0.29 inch of sag at 16 feet instead of 0.49.

Going from a 4x4x1/8 to a 4x4x1/4 nearly doubles the weight, from 6.46 to 12.21 lb per foot, but only raises I from 4.40 to 7.80. It is still less stiff than the lighter 6×2 on edge. Our post on the strength of structural shapes explains the geometry behind this.

Lay the 6×2 flat and its I drops to 1.80, less than a third of the 4x4x3/16.

Rafters follow the same method. Each rafter carries a strip of roof as wide as its spacing, over the run from the ledger to the beam, so closer spacing means a lighter rafter. A rectangular rafter goes on edge too. The engineer or approved plan sets rafter size and spacing.

Posts: what size steel tube for patio cover posts?

Posts are usually square tube, because wind can push on them from any direction and a square tube is equally stiff both ways. Rectangular tube belongs in beams, where the load comes from one direction.

The step from 3×3 to 4×4 is a big one. An HSS 3x3x3/16 has an I of 2.46; an HSS 4x4x3/16 has 6.21. That is about 2.5 times the stiffness for 37 percent more weight (6.87 against 9.42 lb per foot). Which one your plans call for depends on a few things:

  • Height. In California, the patio cover appendix caps covers at 12 feet, and a taller post bends and buckles more easily than a short one.
  • Attached or freestanding. On an attached cover, the ledger and house framing brace one side. On a freestanding cover, the posts act like flagpoles fixed at the ground. Wind bends them hardest right at the base, so the base plate, anchors and footing become engineer territory.
  • Bracing. Knee braces or a rigid frame change how the posts share wind load. Your engineer decides whether they are needed.
  • Vertical load. In the 16 ft example, the beam carries 16 x 6 = 96 square feet of roof, or 960 lb of live load. Split over two posts, that is 480 lb each, plus about 75 lb each for the 4x4x3/16 beam’s own weight. Add panels, rafters and purlins (the cross pieces that hold the roof panels), and a post on a plain slab gets close to the 750 lb limit fast. These are example numbers; your designer adds the real dead load.

Post spacing is the beam span from the worked example: closer posts mean a lighter beam but more bases and footings.

In the desert, wind and connections usually decide the job

On the High Desert valley floor, the published ground snow is 5 psf. In the Mohave Valley below 3,000 feet it is 0. Neither beats the 10 psf patio cover minimum.

Wind is what designs these covers. Late-summer monsoon gusts hit the desert hard, and an open cover acts like a wing: gusts push up under the roof and sideways on the posts. In parts of the Coachella Valley, where Riverside County’s 2021 handout lists a special wind region that may run to 130 mph, uplift can control the design more than gravity does. The weak points tend to be:

  • the post base: base plate, welds and anchor bolts
  • the ledger, where an attached cover ties into the house framing
  • the footing, which has to hold the post down as well as up
  • beam-to-post and rafter-to-beam connections, which see reversing loads in gusts

A 6×3 beam on 4×4 posts can be plenty of steel and still fail at a weak base connection. That is why your engineer will spend more time on connections than on picking the tube.

What to bring to the engineer or the permit counter

First, confirm whether you need a permit. San Bernardino County lists patio covers, solid and lattice, as work that needs a permit. The 120 sq ft exemption in the state code applies to detached accessory structures, and cities amend it. Call your city or county first. Then bring:

  • The site address, so wind and snow can be pulled for your exact spot from the ASCE 7 Hazard Tool
  • Attached to the house or freestanding
  • Overall size, beam span, post spacing and overhang, ideally on a simple sketch
  • Height to the top of the cover
  • Roof material (metal panel, lattice or solid sheathing) and the slope
  • What the posts sit on: existing slab and its thickness, or new footings
  • The tube sizes you have in mind, and that you plan to use A500 structural tube
  • Photos of the wall where a ledger would attach

The engineer returns a member list (beam and post sizes, walls, base plates, anchors), and that list is what you order from.

Ordering the tube from Endura Steel

Once the plans give you a tube list, our carbon tube page covers hot-rolled square tube, galvanized square tube and hot-rolled rectangular tube. Ask about A500 availability for the sizes on your plans, and we can cut pieces to the lengths your drawings call for. If you are building in the Coachella Valley, our guide to cut to size metal for patio covers and shade structures covers metal choice and how to put an order together.

Your next step: send the tube list from your engineer or approved plan through the Get a Quote form, or call the branch nearest your job. Hesperia is (760) 244-5456, Thousand Palms is (760) 343-3100, and Ft. Mohave is (928) 754-7000.

Frequently asked questions

How far can a 4×4 steel tube span on a patio cover?

No code publishes a span for a 4×4 steel tube on a patio cover; an engineer or approved plan sets it. In an illustrative example with 10 psf live load on a 6 ft tributary width, an HSS 4x4x3/16 sagged about 0.49 inch over 16 feet, inside the L/240 limit of 0.80 inch from CRC Table R301.7. That example checks sag only, not wind uplift, buckling or connections.

Is a .120 wall or a 3/16 wall better for patio cover posts?

The 3/16 wall is stiffer: Atlas Tube lists an I of 6.21 in4 for HSS 4x4x3/16 against 4.27 for 4x4x.120. The .120 wall is often sold by gauge, so confirm the decimal thickness on the quote. Posts are also checked for buckling, base plates, anchors and wind uplift, so let the engineer’s calcs pick the wall.

Should rectangular steel tube go on edge or flat for a patio cover beam?

On edge, with the tall side vertical. An HSS 6x2x3/16 has an I of 10.5 in4 on edge but only 1.80 in4 laid flat, so turning it flat throws away most of its stiffness. Flat tube is fine for trim, not for a beam carrying roof load.

Do I need a permit for a steel patio cover?

In most of our area, yes. San Bernardino County and the City of Hesperia both list patio covers as work that needs a permit, and Mohave County requires stamped engineered plans for steel buildings and steel carports, so ask whether a steel cover falls under that rule. The 120 sq ft exemption in the California code covers detached accessory structures and cities change it, so call your city or county first.

Can I use A513 mechanical tube for a patio cover?

It is not a good choice for beams or posts. The Steel Tube Institute notes that ASTM A513 has no minimum yield in its main body and recommends it for nonstructural uses. For structural members, STI points to ASTM A500 Grade C, with a 50 ksi minimum yield.