Choosing rebar for block wall jobs in our area usually comes down to #4 (1/2 in.) bars. The hard part is spacing: on a 6 ft wall it ranges from 48 in. to 16 in., depending on which city or county you build in. Find your jurisdiction’s standard detail first, then order to it.
Take two lots a few miles apart. A 6 ft wall inside Bullhead City limits can go up with one #4 bar every 48 in., per the city’s fence and block wall handout. On a lot in unincorporated Fort Mohave, the Mohave County CMU standards (CMU means concrete masonry unit, the standard gray block) call for #4 every 16 in. with every cell grouted. Same height, about three times as many vertical bars. Monsoon gusts every August are when a weak wall shows it. Endura Steel compared four official details from its branch areas, plus Rancho Cucamonga’s as a typical SoCal template, and turned the four local ones into a steel order.
Rebar for a Block Wall Starts With One Question: Whose Standard?
The line that matters is the city limit. Inside a city, its building department and its standard detail govern. Outside, the county does.
- Thousand Palms, CA is unincorporated, so Riverside County Building & Safety governs and its Freestanding Block Wall standard 284-257 is the detail. Incorporated cities nearby set their own rules, so ask that city.
- Fort Mohave, AZ is unincorporated Mohave County. Block walls under 7 ft on residential lots need no county permit there, but the county publishes a screen wall standard (sheet BW.15) you can build to. The county takes no liability for it and recommends an Arizona-licensed engineer or architect.
- Bullhead City, AZ uses its own handout, effective July 1, 2026. You build to the city detail or to an alternate drawn by an Arizona-licensed registrant (a registered engineer or architect).
- Hesperia, CA has no block wall detail we could find online. Ask Hesperia Building & Safety for its current one. Neighboring Victorville’s standard appears below as a High Desert comparison only.
- Unincorporated San Bernardino County requires a Wall and Fences Permit for any masonry or retaining wall. Engineering calculations may be required.
- Nevada jobs are served from our Fort Mohave branch. A Laughlin lot falls under Clark County, so ask its building department.
One more trap: many cities share a template. Rancho Cucamonga’s BSF-0004 and Gardena’s BLD-1110 carry the same rebar table. Hemet’s 2016 detail is an older edition of the Western Riverside County template, with narrower 6 ft footings.
Key Takeaway: Confirm whether your lot is inside city limits or in the county before you count a single bar.
Same 6 ft Wall, Five Standards
One 6 ft freestanding wall under each standard:
| Standard | Block | Vertical #4 spacing | Grout |
|---|---|---|---|
| Bullhead City, AZ (2026) | 6x8x16 | 48 in. | Steel cells |
| Victorville, CA (2011) | 6 in. min. | 32 in. | Steel cells |
| Riverside County 284-257 (2020) | 6 or 8 in. | 24 in. | Steel cells only |
| Rancho Cucamonga BSF-0004 (2024) | 6 or 8 in. | 24 in. | Steel cells only |
| Mohave County BW.15 (2022) | 8x8x16 | 16 in. | Every cell |
| Standard | Footing (width x depth) | Footing bars | Grade | Design wind |
|---|---|---|---|---|
| Bullhead City | 18 in. x 12 in. (L) or 10 in. (T) | (2) #4 | Not listed | Not listed |
| Victorville | 2 ft 11 in. x 12 in. | (2) #4 | Not listed | Not listed |
| Riverside County | 36 in. (A) or 45 in. (B) x 12 in. | (1) #4 (A) or (2) #4 (B) | 40 min. | 95 mph, Exp. C |
| Rancho Cucamonga | 30 in. (T) or 34 in. (L) x 12 in. | (1) #4 (T) or (2) #4 (L) | 40 min. | 110 mph, Exp. C |
| Mohave County | 24 in. x 10 in. | (3) #4 | 60 | 115 mph, Exp. C |
Reading the codes: T and L name the footing’s shape under the wall (Bullhead City bars the T footing on a property line). A and B are the two footing options on Riverside County’s sheet; build to the one your plan shows.
Every sheet agrees on a few things: #4 bar, a 24 in. minimum lap, grout in each cell that holds steel, and about 3 in. of concrete between the steel and the soil. Rancho Cucamonga, Riverside County and Mohave County also call for bars centered in the cell. Rancho Cucamonga, Riverside County, Bullhead City and Mohave County turn hooks or bends in alternating directions. They disagree on everything that sets the quantity: bar spacing, how many cells take grout, footing width and the bars in the footing. Height matters too. Rancho Cucamonga’s 3 ft through 5 ft 11 in. walls use #4 at 48 in., then the 6 ft row jumps to #4 at 24 in. Riverside County does the same.
Why the Spacing Changes So Much
None of these numbers is a statewide code. Each is one jurisdiction’s standard plan, drawn for the loads it chose.
Design wind
Riverside County’s 2020 detail is designed for 95 mph wind, Exposure C (open terrain with scattered obstructions). Rancho Cucamonga’s 2024 detail uses 110 mph. Mohave County’s 2022 general notes (sheet BW.01) use 115 mph basic wind, Exposure C, with a design wind pressure of 31 psf (pounds per square foot). These are code design wind speeds. All else equal, more wind means more steel.
Steel grade
The California details accept ASTM A615 Grade 40 as a minimum. Mohave County’s notes say reinforcing is furnished as Grade 60. If you build to the county detail, order Grade 60. Our rebar grades guide covers the difference between the two.
Grout and block
Riverside County says outright that its wall “is not designed for all cells to be grouted.” Mohave County’s screen wall says “fully grout all cells” in 8 in. block. Those are two different designs. Don’t pair one standard’s spacing with another’s grout rule or block size.
Corners and free ends
The CMHA (formerly NCMA) TEK 14-16B fence design tables assume a return corner at each end. That is a short wall turning off the end, at least as long as the wall’s exposed height. Where a wall ends with no return, at a gate or driveway opening for example, TEK 14-16B adds 5 psf of design load. The extra load covers a length of wall equal to the exposed height.
Key Takeaway: Spacing follows the wind speed, steel grade and grout rule each standard was designed around, so use one standard’s detail from end to end.
Horizontal Steel: Bond Beams and Joint Wire
Every detail also calls for horizontal steel, and it’s easy to leave off the order. Most of it sits in bond beams: a course of U-shaped block grouted solid around a horizontal bar.
- Riverside County and Rancho Cucamonga: #4 in bond beam block at 32 in. max on center, plus a #4 in the top bond beam.
- Victorville: #4 in a mid and a top bond beam. Bond beams sit 48 in. on center in 6 in. block and 32 in. in 8 in. block.
- Mohave County: one #4 in a fully grouted bond beam at 4 ft max spacing, plus the top course.
- Bullhead City: an 8 in. bond beam with one #4 continuous, shown at about mid-height and at the top. The alternate is ladder-type joint reinforcement at 16 in. on center vertically.
If you go the joint wire route, the Masonry Advisory Council notes the most common joint reinforcement is W1.7 (9 gage) at 16 in. on center. The wire can be no bigger than half the mortar joint thickness. TEK 14-16B also recommends horizontal steel in the top course to help tie the wall together.
Worked Example: Steel for 100 ft of 6 ft Wall
This is example math, not a takeoff for your job. The vertical count is the wall length in inches divided by the spacing, plus one bar for the end:
Verticals = (1,200 in. / spacing) + 1
Example assumptions: a straight 100 ft run with no openings or returns. Each vertical is counted at the wall height only, 6 ft. Footing bars run the full 100 ft. Bond beam rows, each 100 ft: Bullhead 2 (mid-height and top), Victorville 2 (mid and top), Riverside 3 (assumed, to stay within 32 in. max), Mohave 2 (4 ft and top). Weight uses 0.668 lb per foot for #4, from the Caltrans reinforcement table. A real order is longer. It adds the footing embed (Mohave County and Bullhead City put the footing top at least 6 in. below grade, and Mohave shows a 10 in. hook), the hooks, 24 in. laps, and Bullhead City’s separate #4 dowels at 48 in. Ask for the cut list from your detail.
| Standard | Verticals | Vertical ft | Footing ft | Bond beam ft | Total #4 ft | Approx. lb |
|---|---|---|---|---|---|---|
| Bullhead City (48 in.) | 26 | 156 | 200 | 200 | 556 | 371 |
| Victorville (32 in.) | 39 | 234 | 200 | 200 | 634 | 424 |
| Riverside County, A (24 in.) | 51 | 306 | 100 | 300 | 706 | 472 |
| Riverside County, B (24 in.) | 51 | 306 | 200 | 300 | 806 | 538 |
| Mohave County (16 in.) | 76 | 456 | 300 | 200 | 956 | 639 |
A few things push the real number up:
- Laps. Every splice in a footing bar or bond beam bar adds 24 in.
- Corners, ends and openings. Most details want a bar at each end and each side of an opening, so a gate adds bars.
Once you have the counts, our rebar ordering checklist covers how to write the order.
Key Takeaway: On the same 100 ft wall, vertical bars range from 26 to 76, so count from your own jurisdiction’s detail, never from a neighbor’s.
Grout, Laps and Cover: The Details Inspectors Check
Where a permit applies, Rancho Cucamonga and Riverside County list three inspections: footing, rebar before grout, and final.
- Grout in the right cells. Rancho Cucamonga says to grout only the cells and bond beam courses containing rebar. Riverside County calls for grout stop mesh so grout doesn’t run into empty cells. Mohave County wants every cell full.
- Lap length. All five use 24 in. for #4. Mohave County’s lap table goes up to 2 ft 2 in. for #5 and 2 ft 7 in. for #6, if a designer bumps the bar size.
- Cover and support. Rancho Cucamonga wants footing steel supported 3 in. above and away from the soil at the footing inspection. Mohave County shows 2 in. clear at the top of the footing and 3 in. at the bottom. The top of its footing sits at least 6 in. below grade.
- Grade marks. Per CRSI, Grade 60 bar is marked with one line or the number 60.
A note on laps: the Masonry Advisory Council’s lap length paper shows a calculated lap for a centered #4 can come out shorter than 24 in. It also says epoxy-coated bars need 1.5 times the development length (how far a bar must be embedded to carry its full load). Follow the standard you build to, not a calculator.
When the Standard Detail Stops and an Engineer Starts
A standard plan is a shortcut for one common wall. Step outside it and you need a design.
- Too tall. Four of the five details stop at 6 ft, including Mohave County BW.15 and the Bullhead City detail. Victorville’s runs to 7 ft, with #4 at 24 in. and 8 in. block in the first three courses. On a residential lot in Mohave County, a 6 to 7 ft wall needs no permit, but the county detail doesn’t cover it, so it needs a design. Over 7 ft, measured from the lowest adjacent grade, the county requires engineered plans per its residential building page.
- Holding back soil. The California details allow no more than 6 in. of grade difference across the wall and say they are not retaining walls. Mohave County has a separate screen wall detail for up to 1 ft of grade difference, with a 3 ft 3 in. footing and (4) #4. More than that is a retaining wall with its own standard or an engineer.
- Near a slope. Riverside County wants footings next to slopes at least 5 ft to daylight, meaning 5 ft of soil between the footing edge and the slope face.
- Tract walls. Riverside County’s tract block wall process (284-268) caps standard walls at 6 ft and engineered walls at 7 ft. The final needs a structural observation report stamped by a California-registered structural or civil engineer.
- Your own design in Bullhead City. Anything other than the city detail has to be drawn by an Arizona-licensed registrant.
Permit rules differ too. Rancho Cucamonga requires a permit for walls more than 3 ft above adjacent grade. Riverside County’s permit guide lists fences over 6 ft and retaining walls. Bullhead City requires a permit for perimeter fences and walls. It limits single-family walls to 4 ft in the front yard and 6 ft at the side and rear. Mohave County needs no permit for block walls under 7 ft on residential lots, and limits fencing to 4 ft for the first 15 ft from the front property line. No permit means no inspector, so the risk sits with the owner. Build to the county detail anyway.
Order Block Wall Rebar From Endura Steel
Start with your detail: the city or county standard for your parcel, or your engineer’s drawing. Pull the bar size, spacing, footing bars and bond beam rows from it, count them for your wall length, and send us the list. Our rebar team can cut, bend, and shape rebar to your project’s exact engineering specifications, so dowels, hooks and straight bars show up ready to set. For a Mohave County wall, ask about Grade 60 availability when you call.
- Call Ft. Mohave, AZ: (928) 754-7000
- Call Thousand Palms, CA: (760) 343-3100
- Call Hesperia, CA: (760) 244-5456
- Get a Quote through the contact form
Your success is our success.
Frequently asked questions
Do I need rebar in every cell of a block wall?
It depends on whose standard you build to. The California details in Riverside County, Rancho Cucamonga and Victorville put #4 bars at 24 to 32 in. on a 6 ft wall and grout only the cells that hold steel. Mohave County’s published screen wall detail puts #4 every 16 in. and grouts every cell, so use the detail for your lot.
Can I use a garden wall detail for a retaining wall?
No. The Riverside County and Rancho Cucamonga block wall details allow no more than 6 in. of grade difference across the wall and say they are not retaining walls. Mohave County has a separate screen wall detail for up to 1 ft of grade difference; anything beyond that needs a retaining wall standard or an engineer.
How long should rebar laps be in a block wall?
All five standards compared here use a 24 in. minimum lap for #4 bar. The Masonry Advisory Council’s lap length paper notes that matches the old 48 bar diameter rule, a fixed number you can check on site. Epoxy-coated bar needs a longer development length, so ask your designer if you plan to use it.
Do I need a permit for a block wall in Mohave County?
In unincorporated Mohave County, including Fort Mohave, block walls under 7 ft on residential lots need no permit, and walls over 7 ft need engineered plans. The county’s published detail stops at 6 ft, so a taller wall still needs a design. Inside Bullhead City limits a permit is required for perimeter fences and walls.
Should I use Grade 40 or Grade 60 rebar for a block wall?
Use what your standard calls for. The California details here accept ASTM A615 Grade 40 as a minimum, while Mohave County’s standards call for Grade 60. Grade 60 bar is marked with one line or the number 60, which makes it easy to check at delivery.